Device installation

7.2.4.3.1 In the alarm output "ON" l configuration setting

see menu description,
Jumper setting
Closing function:
(Default setting)
Opening function:

7.2.4.3.2 In the alarm output "OFF" m configuration setting

Ä Chapter 10.3.9 'Configuration / Alarm output' on page 77).
(
Jumper setting
Closing function: (Default
setting)
Opening function:
* fail-safe function, (safe in the event of failure)
417101442 Rev. 12-02.2019
Ä Chapter 10.3.9 'Configuration / Alarm output' on page 77).
If "No Alarm"
(Alarm relay has not
pulled in)
contact open
contact closed
If "No Alarm"
(Alarm relay has
pulled in)
contact closed
contact open
46
If "Alarm"
Power Off
(Alarm relay has
(Alarm relay has not
pulled in)
pulled in)
contact closed
contact open
If "Alarm"
(Alarm relay has
not pulled in)
contact open
contact closed
contact open
contact closed
Power Off
Power Off (Alarm
relay has pulled in)
contact open
contact closed