10.3.3. Heating time slot (time programming)
This parameter defines the permissible time slots for starting the heat pump and the electric backup
in accordance with the hot water requirements. It can be configured if there is no connection to the off-peak
signal, or to the PV own consumption signal.
The configuration is made for each day of the week. A day must include between one and three time slots
totalling at least 8 hours of heating. Settings are made in 15-minute increments.
Examples:
10.3.4. Electric backup
This menu is used to set the electric heating element authorisation time:
• as little as possible: only outside the heat pump's operating range or in the event of a heat pump fault
• to secure the quantity of hot water: in addition to the heat pump to guarantee a sufficient volume
of hot water
10.3.5. Setpoint management
This function is used to select the mode:
• Eco+: the water heater autonomously programs consumption to adapt to the user's needs, and save
energy while guaranteeing comfort. In this mode, the user has no control over the setpoint and it is not
visible on the HMI. The water heater automatically adjusts the setpoint based on the usage.
• Manual: the user can set the water heating temperature to between 55 °C and 65 °C.