5.4
Individual control in combination with RT 800
The individual control feature and the RT 800 (from software version
PF21.04, produced from approx. 11/2023) can also be used in the
same heating circuit. This is an exception, as other remote controls can
otherwise only be used in other heating circuits ( Chapter 3). If the
individual control and RT 800 are assigned to the same heating circuit,
this heating circuit is controlled by the individual control (e.g. flow
temperature). With regard to functions and displays of the RT 800
( Operating instructionsRT 800).
There is no provision for operating the individual control (e.g. changing
the set room temperatures) using RT 800. This is possible with the
Bosch HomeCom Easy app ( Chapter 6.3).
Commissioning sequence for individual control and RT 800
If the individual control and RT 800 are to be assigned to the same
heating circuit, proceed as follows during installation and
commissioning:
▶ Select UI 800 in the desired heating circuit, Remote control >
Individual control ( Chapter 4.2.1).
▶ Then start the RT 800 configuration, select RT 800 in the same
heating circuit and continue commissioning ( Operating
instructions RT 800).
The RT 800 recognises the individual control when commissioning is
started and carries out a pre-configuration.
If the RT 800 and the individual control are assigned to the same heating
circuit, the RT 800 can no longer work as a remote control for a second
heating circuit. For this purpose, assign the RT 800 to a heating circuit
that is not configured for individual control.
If the RT 800 was already configured before the individual control was
configured and the individual control and the RT 800 are to be assigned
to the same heating circuit, the RT 800 must be reset to the factory
settings:
▶ Reset RT 800 on RT 800 to factory settings ( Operating
instructions RT 800).
▶ Select UI 800 in the desired heating circuit, Remote control >
individual control ( Chapter 4.2.1).
▶ Then start the RT 800 configuration, select RT 800 in the same
heating circuit and continue commissioning ( Operating
instructions RT 800).
If the individual control and RT 800 are assigned to different heating
circuits, no specific procedure needs to be followed during installation
and commissioning.
SRC 100 RF – 6721856014 (2024/11)
6
Detailed functional description
6.1
Individual room temperature-dependent control
The individual controls control the room temperature by regulating the
heating water volume flow in the respective radiators or the underfloor
heating system.
The individual controls have 2 operating modes for room temperature-
dependent control, Manual a~nd Auto. These can be set individually for
each individual control or group of room controls (individual controls
grouped in one room, e.g. 3 units).
• Manual:
in manual mode, the room temperature-dependent control is
controlled according to the set room temperature set for each
Individual control or group of individual controls. The set room
temperature can be set directly on the Individual control or in the
Bosch HomeCom Easy app.
• Auto:
in automatic mode, the room temperature-dependent control is
controlled according to the set time program (weekly profile). The
time program can be set individually in the Bosch HomeCom Easy
app for each individual control or group of individual controls. The set
room temperature can be changed manually at any time directly on
the individual control or in the Bosch HomeCom Easy app. The
manual temperature change remains active until the next switching
point of the time program is reached.
6.2
Grouping individual controls
The EasyService app or the app Bosch HomeCom Easy can be used to
group individual controls in a room. For this purpose, the corresponding
individual controls must simply be assigned to the same room. All
individual controls in the same assigned room automatically synchronise
their settings (e.g. set room temperature, time program, operating
mode, button lock, etc.).
sec
2 0 ,5 °
0010054001-001
Fig. 17
If, for example, the set room temperature is changed on an individual
control in a group (room), this new set room temperature is transferred
to all individual controls in this group (room). It is not necessary to make
the setting individually on each individual control. If the set room
temperature is changed in an app, this change always applies room by
room for all individual controls in this group (room).
Detailed functional description
2 0 ,5 °
1 9 ,0 °
2 0 ,5 °
1 9 ,0 °
2 0 ,5 °
1 9 ,0 °
2 0 ,5 °
2 0 ,5 °