DESCRIPTION OF THE UNIT

MACHINE PURPOSE
The fan coil is a room air treatment terminal unit for both winter and summer operation.
FCLI VERSION
Cassette-type fan coil with Inverter for installation in suspended ceilings; can be integrated in standard 600x600.
AVAILABLE SIZES
The cassette-type fan coils of the FCLI range are available in:
for 2-pipe systems
FCLI 32 (600x600)
FCLI 42 (600x600)
FCLI 62 (600x600)
GRILLE UNIT (OBLIGATORY ACCESSORY)
GLLI100/GLFI10/GLLI100N/GLFI10N/GLFI10M/GLLI100EH/GLFI10EH: Grille unit with suction and delivery filter, with manually adjustable fins;
requires an external control panel with thermostat and ventilation speed control, with 0-10V output.
TECHNICAL DATA AND OPERATING LIMITS
Maximum recommended temperature
Maximum water inlet temperature
Maximum operating pressure
Minimum operating pressure
Room temperature limit R.T.
Room temperature limit R.H.
Minimum delivery (heating)
Maximum delivery (heating)
Minimum delivery (cooling)
Maximum delivery (cooling)
Maximum input current
Power supply
Performance values refer to the following conditions:
- at the maximum motor speed;
Water temperature
In order to prevent air stratification in the room,
and therefore to achieve improved mixing, it is
advisable not to supply the fan coil with water at
Minimum average water temperature
If the fan coil is working in continuous cooling
mode in an environment where the relative
humidity is high, condensate might form
on the air delivery and on the outside
of the device. This condensate might be
MINIMUM AVERAGE WATER TEMPERATURE [°C]
Ambient air temperature
with wet bulb
For 4-pipe systems
FCLI 34 (600x600)
FCLI 44 (600x600)
FCLI 64 (600x600)
FCLI
°C
°C
°C
°C
A
V / Hz
- the total input power is determined by adding the input power for the
unit to the input power for the accessories connected and declared in
the corresponding manuals.
a temperature over 65°C.
The use of water at high temperatures could
cause squeaking due to the different thermal
expansions of the elements (plastics and metals),
deposited on any objects underneath and
on the floor.
To avoid condensate on the external structure
of the apparatus with the fan in operation,
the average temperature of the water must
not be lower than the limits shown in the
15
17
19
21
23
32
34
42
65°C
80°C
kPa 800 (8 bar)
kPa 100 (1 bar)
<Ta<40
0°C
°C
< 85%
R.H.
100
50
100
750
400
750
100
100
100
750
750
750
0.22
0.22
0.33
230V (±10%) 50 Hz
this does not however cause damage to the unit
if the maximum operating temperature is not
exceeded.
table below, that depend on the thermo-
hygrometric condition of the air in the envi-
ronment.
The limits mentioned above refer to operation
while the fan is set
to its minimum speed level.
Ambient air temperature with dry bulb
21
23
25
3
3
3
3
3
3
3
3
3
6
5
4
-
8
7
44
62
64
50
150
50
400
1050
400
100
150
150
750
1050
1050
0.33
0.37
0.37
27
29
31
3
3
3
3
3
3
3
3
3
3
3
3
6
5
5
15