Failure Code
Failure Code
Outdoor Digital
Indoor Wired
Display Tube
Controller
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20-0
21
22
23
26
28
29
30
33
34
35
38
39-0
39-1
40
E01
Water Inlet Temperature Sensor Twi Abnormality
E02
Water Outlet Temperature Sensor Two /Tout2 Abnormality
E03
Liquid Pipe Temperature Sensor Thi Abnormality
E04
Gas Pipe Temperature Sensor Tho Abnormality
E05
E06
Communication error with outdoor unit
Communication Error between Remote Wired Controller
E07
E08
Flow Switch/ Flowmeter Abnormality
E09
DHW tank temperature sensor T_tank up/T_tank down
E10
E11
ATW-A02 Communication Abnormality
Zone2 mixing valve temperature sensor Twzone_2
E12
E13
E14
Low Pressure Switch Abnormality (reserved)
E15
E16
Water Inlet/Outlet Temperature Over High
Zone1 indoor ambient temperature sensor abnormality
E17
Zone2 indoor ambient temperature sensor abnormality
E18
Pool mixing valve water outlet/pool water temperature
E19
E20-0
Defrosting temperature sensor Te(1) abnormality
E21
Outdoor ambient temperature sensor Tao abnormality
E22
Suction temperature sensor Ts abnormality
E23
Discharge temperature sensor Td abnormality
E26-0
Communication error with HU/ATW-A03N
E28
Compressor Discharge Pressure Sensor Pd Abnormality
E29
Compressor Suction Pressure Sensor Ps Abnormality
E30
High Pressure Switch HPS Abnormality
E33
Outdoor Unit PCB EEPROM Abnormality
Compressor Discharge Temperature Over High
E34
E35
Four Way Valve Reversing Abnormality
E38
E39-0
E39-1
E40
Error Code Definition
EEPROM Abnormality
and ATW-A03N
Duplicate ATW-A03N address
abnormality
abnormality
Water Leakage (reserved)
Anti-freeze Abnormality
(reserved)
(reserved)
sensor abnormality (optional)
Protection(Td)
High pressure Pd too low
Low pressure Ps too low
Compression ratio ε too high
High pressure Pd too high
40
Remarks
Automatic
Automatic
Automatic
Automatic
Manual
Automatic
Automatic
Automatic (less than three alarms
within 60 mins); otherwise, Manual
Manual
Automatic
Automatic
Automatic
Manual
Automatic
Automatic (less than three alarms
within 60 mins); otherwise, Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic (less than three alarms
within 60 mins); otherwise, Manual
Manual
Automatic (less than three alarms
within 60 mins); otherwise, Manual
Automatic (less than three alarms
within 60 mins); otherwise, Manual
Automatic (less than three alarms
within 60 mins); otherwise, Manual
Automatic (less than three alarms
within 60 mins); otherwise, Manual
Automatic
Automatic (less than three alarms
within 60 mins); otherwise, Manual