6 Commissioning
!
70
6.4.4
Programme selection
Note!
You can only select switching and event programmes in the 7-programme module.
Menu structure:
Fig. 19:
Programme selection menu structure
Several programme combinations are available for the 7 programme version:
1
A main programme is active.
2
A main programme and a switching programme are active.
1+Event
A main programme and the event programme are active.
2+Event
A main programme, a switching programme and the event programme are active.
Main programmes
Four main programmes are available. Select a main programme from the item PROG. NAME. (See
"Creating a main programme" on Page 71.)
Switching programmes
Two programme pairs (1⇔U1 and 2⇔U2) are available. The switching programmes (U1 and U2)
are permanently assigned to the main programmes (1 and 2). You can trigger a switch from the main
programme to the switching programme as follows.
Day
Switch to the switching programme at two settable times in one day.
Week
Switch to the switching programme on three settable days in the week.
Q greater
Switch to switching programme on exceeding a settable threshold value.
!
A quantity signal must be connected to the analog input of the sampler for this function.
Q smaller
Switch to switching programme on undershooting a settable threshold value.
Note!