Herunterladen Diese Seite drucken

AEG ME10 Handbuch Seite 27

Leistungsschalter

Werbung

1.3.4: Typical Connection Arrangement
1.3.4: Typische Anschlusskonstellation
1.3.4: Connessioni standard
Rondella di sicurezza
Customer bus
Anlagen-Schiene
Sbarre
Customer bus
Anlagen-Schiene
Sbarre
Plain Washer (Heavy duty)
Unterlegscheibe
Rondella piana (heavy duty)
Breaker type 'Automatic'
Switch Type
Leistungsschalter
Leistungstrenner
Interruttore tipo 'Automatico' Tipo interruttore
--------------------------------------------------------------------------------------------------------------------------------------------------
AT04, R & K
A704R
AG04, S N & H
AJ04S & AW04N
AG04 E & M
AJ04H
AT07, R & K
A707R
AG07, S N & H
AJ07S & AW07N
AG07 E & M
AJ07H
AT08, R & K
A708R
AG08, S N & H
AJ08S & AW08N
AG08 E & M
AJ08H
AT10, R & K
A710R
AG10, S N & H
AJ10S & AW10N
AG10 E & M
AJ10H
AT13, R & K
A713R
AG13, S N & H
AJ13S & AW13N
AG13 E & M
AJ13H
AT16, R & K
A716R
AG16, S N & H
AJ16S & AW16N
AG16 E & M
AJ16H
AG20, S N & H
AJ20S & AW20N
AG20 E & M
AJ20H
AG25N, H & M
AJ25N & AW25H
AG32N, H & M
AJ32N & AW32H
AH32N, H & M
AK32N & AZ32H
AG32G & L
AJ32G
AG40N, H & M
AJ40N & AW40H
AH40N, H & M
AK40N & AZ40H
AG40G & L
AJ40G
AG50M & L
CJ50L
AG64M & L
CJ64L
Lock Washer
Federring
Envelope
Baugröße
Taglia
T
1 or 2
1 or 2
T
1 or 2
1 or 2
T
1 or 2
1 or 2
T
1 or 2
1 or 2
T
1 or 2
1 or 2
T
1
2
1
2
2
2 or 3
2 or 3
2 or 3
2
2
3
3
3
Hex Bolt (8.8)
Anschlussschraube
Vite esagonale (8.8)
Breaker terminal
Leistungsschalter-Schiene
Terminale dell'interruttore
Hex Nut (8.8)
Schraubenmutter
Dado esagonale (8.8)
In (A)
Recommended Copper Bus Bar sizes
In (A)
Kupferschienenquerschnitte
In (A)
Dimensioni raccomandate sbarre in rame
400
1 x 30 x 10 or 2 x 30 x 5
400
1 x 40 x 10 or 1 x 80 x 5 or 2 x 40 x 5
400
1 x 40 x 10 or 1 x 80 x 5 or 2 x 40 x 5
630
1 x 40 x 10 or 2 x 40 x 5
630
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
630
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
800
1 x 50 x 10 or 2 x 50 x 5
800
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
800
1 x 50 x 10 or 1 x 100 x 5 or 2 x 50 x 5
1000
3 x 40 x 5
1000
1 x 60 x 10 or 2 x 60 x 5
1000
1 x 60 x 10 or 2 x 60 x 5
1250
2 x 40 x 10 or 4 x 40 x 5
1250
2 x 40 x 10 or 2 x 80 x 5
1250
2 x 40 x 10 or 2 x 80 x 5
1600
2 x 50 x 10 or 4 x 50 x 5
1600
2 x 50 x 10 or 2 x 100 x 5
1600
2 x 50 x 10 or 2 x 100 x 5
2000
3 x 50 x 10 or 3 x 100 x 5
2000
3 x 50 x 10 or 3 x 100 x 5
2500
4 x 50 x 10 or 4 x 100 x 5
3200
4 x 100 x 10
3200
4 x 100 x 10
3200
4 x 100 x 10
4000
4 x 100 x 10 + 1 x 100 x 5
4000
4 x 100 x 10 + 1 x 100 x 5
4000
4 x 100 x 10
5000
5 x 120 x 10 or 6 x 100 x 10
6400
7 x 120 x 10 or 8 x 100 x 10
BREAKER
BREAKER ME10
Recommended Connection Cross
The adjacent table indicates the
recommended bus bar dimensions
to be used in connecting the
ME10 Power Circuit Breaker.
Vorgeschlagene
Leiterquerschnitte:
Die nebenstehende Tabelle zeigt die
vorgeschlagenen
Schienenanschluss-Querschnitte
der verschiedenen
ME10 Leistungsschalter.
Sezioni trasversali consigliate
delle connessioni
La tabella a lato indica le
dimensioni raccomandate delle
sbarre da utilizzare per la
connessione dell'interruttore
1
.3
sections
aperto ME10
1.3-05

Werbung

Kapitel

loading