Toshiba MCY-MAP0401HT2D Installations-Handbuch Seite 37

Außengerät mini-smms klimasystem
Vorschau ausblenden Andere Handbücher für MCY-MAP0401HT2D:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 82
• To change all the indoor addresses from an arbitrary wired remote controller.
(When the setup operation for automatic address has finished, this change is available.)
Contents : Using an arbitrary wired remote controller, the indoor unit address can be changed for each unit within
the same refrigerant system.
* Change the address in the address check/change mode.
[Procedure] (Operation while air conditioner stops)
1
Push the timer time
Firstly, the line 1, item code
2
UNIT
Using
/
SWING/FIX
buttons, select the line address.
3
SET
Push
button.
• The indoor address, which is connected to the refrigerant system of the selected header unit is displayed and
the fan is turned on.
First the current indoor address is displayed on the setup data. (Line address is not displayed.)
4
The indoor address of the setup data moves up/down by the timer time
Change the setup data to a new address.
5
SET
Push
button to determine the setup data.
6
UNIT
Every pushing
displayed. Only fan of the selected indoor unit operates.
Repeat the procedure
7
SET
Push
button.
(All the displays on LCD go on.)
8
TEST
Push
button to finish the procedure.
SET
DATA
SETTING
UNIT No.
R.C.
TEMP.
TIMER SET
1
TIME
FILTER
RESET TEST
SET CL
3
Deletion of line selection
Here, if the unit No. is not called up, the
header unit in this system does not exist.
CL
Push
button, and then select a line
according to procedure
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
TEST
+
buttons simultaneously for 4 seconds or more.
AC
(Address Change) is displayed.
button, the indoor unit numbers in the same refrigerant line are successively
4
6
to
and change all the indoor addresses so that they are not duplicated.
CODE No.
No.
ON / OFF
FAN
MODE
SWING/FIX
VENT
2
UNIT
2
.
www.heronhill.co.uk
SET
DATA
SETTING
TEMP.
4
FILTER
RESET TEST
8
5, 7
Operation procedure
®
®
®
®
1
2
3
4
34
/
buttons.
CODE No.
UNIT No.
R.C.
No.
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET CL
UNIT
To finish the set
®
®
®
5
6
7
8
Fax: 01823 665807
6
End