DANGER
Danger from malfunction!
In the event of a battery error
message/contamination message,
the smoke alarm device may
only continue to provide its reliable
warning performance for max. 60
days .
f Ensure that the device is replaced
before the remaining 60 days have
passed .
Battery error message
A battery error message is triggered
when the device starts using its energy
reserves. During a battery error mes-
sage, a single tone will sound every 90
seconds (see chapter 17 "Alarm and
alert tones" on page 83). Proceed as
follows:
(1) Press testing/stop button to turn off
the battery error message for
24 hours.
(2) Replace the device.
72
User Manual: XSD200 - Smoke Alarm Device with Radio Link
Contamination message
A contamination message is trig-
gered when the readjustment of the
detection electronics is no longer pos-
sible due to heavy soiling. During the
c o n t a m i n a t i o n m e s s a g e , a d o u -
ble tone will sound every 90 seconds
(see chapter 17 "Alarm and alert tones" on
page 83). Proceed as follows:
(1) Press testing/stop button to turn
off the contamination message for
24 hours.
(2) Replace the device.
Alarm without cause of fire
An alarm without fire is triggered under
the following circumstances:
Regular dust formation in
living spaces with textiles prone
to accumulate dust (e.g. carpets,
clothing, blankets and pillows)
Pollen, construction,
sanding or fine dust
Insects or micro-organisms
that have overcome the insect
EN
EN