13. Installing controller
13.9 Checking temperature sensors
The temperature sensors may be checked by measuring resistance at a specific
temperature. If any significant differences are observed between the measured
resistance and the values in the table below, replace the sensors.
CT4
Ambient Temp. [°C]
Min. [Ω]
0
10
20
25
30
40
50
60
70
80
90
100
CT6-P (weather compensator)
Ambient Temp. [°C]
Min. [Ω]
0
25
1096,9
50
1193,4
100
1384,2
125
1478,5
150
1572,0
13.10 Connecting boiler room thermostat
Room thermostat for boiler circuit will disable burner or CH boiler pump. For the
room thermostat to shutdown the boiler, set Select thermostat to Universal or
ecoSTER T1, if ecoSTER TOUCH room temperature controller is installed.
Service settings > Boiler settings > Select thermostat
For the room thermostat to disable CH boiler pump without disabling the
burner, set parameter: YES
13.11 Connecting auxiliary boiler
The controller can control auxiliary gas or oil burner operation.
The auxiliary boiler is enabled automatically in the event of the main boiler
alarm that prevents its operation or if the temperature in the main boiler
decreases. The auxiliary boiler, e.g. gas boiler must be connected by a qualified
installer in accordance with the boiler documentation. The auxiliary boiler
should be connected via a relay to the terminals 46-47.
Leader in pellet boilers
Nom. [Ω]
Max [Ω]
815
802
828
886
874
898
950
961
972
990
1000
1010
1040
1029
1051
1108
1122
1136
1192
1209
1225
1299
1278
1319
1369
1392
1416
1462
1490
1518
1591
1559
1623
1659
1696
1733
Nom. [Ω]
Max [Ω]
999,7
1000,0
1000,3
1097,3
1097,7
1194,0
1194,6
1385,0
1385,8
1479,4
1480,3
1573,1
1574,2
Example wiring diagram:
1- controller,
2 – auxiliary boiler (gas or oil),
3 – RM 84-2012-35-1012 relay and GZT80 RELPOL socket.
Standard controller does not include a relay. Auxiliary boiler control is enabled
by setting H output function to Auxiliary boiler.
Service settings > Output H > Output H function
The auxiliary boiler is disabled by removing voltage from terminals 46-47.
The auxiliary boiler is enabled by supplying voltage to terminals 46-47.
Wiring diagram for
auxiliary boiler
valve control:
1 – controller,
2 – auxiliary boiler,
3 – relay,
5 – valve actuator (with limit switches).
Note: terminals 22, 21, 24
must be separated from terminals
12, 11, 14.
ecoMAX860P3-S – Simple Controller User Manual – EN 12.17