14 ALARMS MEMORY

On entry to the alarms memory page the data inherent the last alarm acquired is displayed. Use the
1. ALARM: description of the anomaly
2. INDEX: indicates the alarm index
3. ORIGIN: indicates which element has generated the alarm (Chiller, i_th Fan Coil, DHW, System, VMF-CR, VMF-P1, VMF-P2, VMF-P3, MZC, VMF-REB 1/2/3)
4. DATE TIME: indicates the time and date when the alarm occurred
To delete the alarms log, press the
dure all of the alarms present in EEPROM are removed, otherwise the memory remains unvaried. With complete memory (max 5 alarms), if a new event occurs, the storage
process will automatically delete the oldest alarm and enter the new one under index 10.
The Enter
key has no function on this page.
Press the
key for the system to display the menu page.
ORIGIN
ALARM
System
EEPROM error
Not connected
Air-water chiller
Machine fault
Faulty room probe
Anti-freeze
Insufficient water
Fancoil
Interface not connected
Inverter fault
Not connected
Not connected
No anti-legionella
D.H.W.
Resistance fault
Probe fault
No hot water
Boiler fault
M. c. r.
Not connected
M. P. 1
Not connected
M. P. 2
Not connected
M. P. 3
Not connected
MZC
Not connected
VMF-REB 1
Not connected
VMF-REB 2
Not connected
VMF-REB 3
Not connected
Key:
— System = VMF-RCC panel
— Chiller = chiller unit or heat pump
— Fancoil = i_th fan coil thermostat
— D.H.W. = DHW panel
— M.c.r. = accessory for controlling the boiler and recovery units
— M.P.1 = VMF-CRP accessory for controlling circulator pumps 1, 2 , 3, 4
— M.P.1 = VMF-CRP accessory for controlling circulator pumps 5, 6, 7, 8
— M.P.1 = VMF-CRP accessory for controlling circulator pumps 9, 10, 11, 12
— MZC = plenum of the i_th fan coil unit
— VMF-REB 1 = to control up to 10 different heads of the radiant system with the fan coil thermostats
— VMF-REB 2 = to control up to 10 different heads of the radiant system with the first 10 MZCUI user interfaces
— VMF-REB 3 = expansion accessory for controlling the radiant heads associated with the areas where MZCUIs are located
68
1
4
key, which leads to the display of a screen where the confirmation of the operation is requested. Only by continuing with the proce-
This alarm may appear when the panel is switched on for the first time or when the EEPROM has a malfunction
Check the address (200) and the RS485 bus for proper connection
View the alarm specified by the machine control
Check thermostat room probe
Due to environmental conditions
Due to unfavourable system conditions
Check the VMF-E2/E4 panel attached to the relevant thermostat for proper connection or electrical integrity
Check the inverter functioning or wiring reporting the inverter state to the thermostat
Check correct RS485 bus connection
Check address (1) and the RS485 bus for proper connection.
Due to unfavourable system conditions (heat pump, exchanger or resistance in the storage tank)
Check the resistance for intactness, the status of the magnet circuit breaker in the DHW panel or input (ID1-ICD1 terminal
board J4 of the PCOe in the DHW panel)
Check the connection and status of the water probe
Due to unfavourable system conditions (heat pump or exchanger in the storage tank)
Check the boiler or the presence of the input for reading (ID1-ICD1 terminal board J4 of the PCOe)
Check address (2) and the RS485 bus for proper connection
Check address (3) and the RS485 bus for proper connection
Check address (4) and the RS485 bus for proper connection
Check address (5) and the RS485 bus for proper connection
Check address (1) and the RS485 bus for proper connection.
Check address (1) and the RS485 bus for proper connection.
Check address (1) and the RS485 bus for proper connection.
Check address (1) and the RS485 bus for proper connection.
2
3
and
keys to scroll the logged events.
CAUSE OF THE ALARM
23/03 – VMF-RCC_UN50_01