— Edit the chiller water output set during winter functioning. The acceptable values range from 0.0 to 20.0 [°C].
Level: user.
— Edit the parameter that identifies the band of values in which the chiller water output set can vary during summer functioning if the Economy environment control has
been enabled. The acceptable values range from 3.0 to 20.0 [°C].
Level: user.
To enter the data editing mode, press the
The data is confirmed by pressing the enter (
Press the
key for the system to display the menu page.
Using the Page Up
and Page Down
SET CHANGE PARAMETERS PAGE
Use this page to change the frequency and the increase/decrease in the correction of the generator water output set when the "ECONOMY" control is enabled: the system will
check the actual load required by the fans coils at ?t intervals and change the machine set through the VMF algorithm to minimize the system's power consumption.
Key to enable load control (VMF algorithm).
Δt = The acceptable values range from 1 to 60 min
Δ+ = The acceptable values range from 0.1 to 2.0 [°C]
Δ- = The acceptable values range from 0.1 to 2.0 [°C]
23/03 – VMF-RCC_UN50_01
key. This status is highlighted if no string is displayed. To change the value, act on the increase (
) key, while the effective memorisation in EEPROM is highlighted by the disappearance of the denied display.