Dhw Set Page; Anti-Legionella Treatment Page - Aermec Vmf-Rcc Zubehörhandbuch

Vorschau ausblenden Andere Handbücher für VMF-RCC:
Inhaltsverzeichnis
Verfügbare Sprachen
  • DE

Verfügbare Sprachen

The VMF-DHWxxx accessory may not be managed if multiple chiller/heat pump units are controlled by the Multicontrol system. Under these conditions,
DHW is managed by the Multicontrol system through the VMF-CRP1/VMF-CRP2 expansion.

DHW SET PAGE

On this page you can view and/or modify the parameter:
— The "Water temperature" parameter, namely the temperature set for DHW, can be viewed and or edited. The range of acceptable values is 0 ÷ ("Chiller set for DHW" – "Heat
differential" ) [°C].
— Functioning according to daily time periods for domestic hot water. If the "DHW program" is set to ON, only the scenario described under "DHW PRG" in the time periods
menu may be associated to DHW.
— "On/Off Band", namely the hysteresis between the maximum and minimum temperature that DHW can assume. The range of acceptable values is 0 ÷ ("Chiller set for DHW"
– "Heat differential" - "Water temperature")[°C]. This parameter is used in concomitance with the "Water temperature" to establish the switch-on and switch-off thresholds
of the production of DHW.
To enter the program editing mode, press the
(
) keys. The data is confirmed by pressing the enter (
Press the
key for the system to display the menu page.
Using the Page Up
and Page Down

8.2 ANTI-LEGIONELLA TREATMENT PAGE

This page is used to display and set all parameters inherent to the anti-legionella cycle, to be carried out on the water of the storage tank.
1. START TIME: anti-legionella cycle start time
2. ENABLING DAYS: days on which the start of the anti-legionella cycle is enabled (
Press the
key for the system to display the menu page.
The icon
indicates that the anti-legionella cycle is enabled. Pressing the button disables the functioning of the same and the changing of the image into
The icon
indicates that the anti-legionella cycle is disabled. Pressing the button enables the functioning of the same and the changing of the image into
Using the Page Up
and Page Down
23/03 – VMF-RCC_UN50_01
key. This status is highlighted when no parameter is displayed. To change the value, act on the increase (
) key, while the effective memorisation in EEPROM is highlighted by the disappearance of the denied display.
keys, scroll the pages contained in the sub-menu.
1
keys, scroll the pages contained in the sub-menu.
enabled,
disabled).
) and decrease
2
.
.
47