1.5.3 Max. Leitungslänge und -querschnitt
Cable section [mm
Max Length m [feet]
1.6 LISTE DER BRÜCKEN AUF DER REGLERKARTE
Designation
S5 - S6
Terminating resistor for the serial interface RS485
ON= Termination resistor IN
OFF= No termination resistor
Adaptation to the input signal of analog input 1 (terminals 1 and 2)
S8
ON=0...20 mA / 4...20 mA
OFF=0...10 V / -10...+10 V
S9
Adaptation to the input signal of analog input 2 (terminals 3 and 4)
ON=0...20 mA / 4...20 mA
OFF=0...10 V / -10...+10 V
S10
Adaptation to the input signal of analog input 3 (terminals 5 and 6)
ON=0...20 mA / 4...20 mA
OFF=0...10 V / -10...+10 V
S11 - S12 - S13
Encoder setting ( jumpers on kit EAM_1618 supplied with the drive)
S14 - S15 - S16
ON=Sinusoidal SE
OFF=Digital DE
S17
Monitoring of the C-channel of the digital encoder
ON=C-Channel monitored
OFF=C-Channel not monitored (required for single-ended channels)
S18 - S19
Encoder setting
S20 - S21
Pos. B= reserved
Pos. A= reserved
S22 - S23
Analog input 3 enabling (alternative with SESC encoder)
Pos. A= reserved
Pos. B=analog input 3 enabled
Pos. OFF= resolver
S26 - S27
Reserved
Encoder Internal power supply selection
S28
ON / ON = +5 V
OFF / OFF = +8 V
S29
Internal use
Second encoder qualifier input
S30
A=from EXP-... board
B=from digital input "3" on RV33-4
S34
Jumper to disconnect 0V (+24V power supply) from ground
ON = 0V connected to ground
OFF = 0V disconnected from ground
S35
Jumper to disconnect 0V (regulation board) from ground
ON = 0V connected to ground
OFF = 0V disconnected from ground
S36
Internal use
S37
Internal use
S38-S39
Internal use
S40-S41
Power supply for the serial interface RS485
ON = Internal power supply (from pins XS.5 / XS.9)
(**)
OFF = External power supply (to pins XS.5 / XS.9)
(*)
on multidrop connection the jumper must be ON only for the last drop of a serial line
see chapter 5.4
(**)
GR
16
2
]
0.22
0.5
27 [88]
62 [203]
Function
AVy -HD
——————
0.75
1
93 [305]
125 [410]
——————
1.5
150 [492]
avy3130
Factory setting
ON (*)
OFF
OFF
OFF
OFF
OFF
B
B
ON
ON/ON
A
A
ON
(hard-wire)
ON
(hard-wire)
not mounted
not mounted
ON
OFF
Ay4060