The limit for the temperature can be adjusted from OFF - 99°C
(pre-set from works: OFF).
Adjustment temperature limit:
1. Activate the menu "TEMPERATURE MINIMUM:"
2. Select the desired value with
3. Press NEXT to confirm.
The time delay can be adjusted from 0 to 9999 s in steps of 1 s
(adj. from works: 0120 s).
NOTE
The alarm delay time can only be set in connection with a set limiting value (> OFF).
Adjustment time delay:
1. Activate the menu TEMPERATURE DELAY.
2. Select the desired value at the flashing position with
3. Select the appropriate position by ↵.
4. Press NEXT to confirm.
9.4.6
Alarm repeat time
Determining an alarm repeat time (ALARM REPEAT TIME): OFF) can prevent an alarm
that has already been acknowledged – without the fault having been rectified from being
forgotten.
The fault message output is always activated again after acknowledgement and after the
time set has passed (so long until the fault has been rectified).
The alarm repeat time can be set from OFF up to 999 minutes in increments of 1 minute
(factory setting is OFF).
The alarm repeat time is to be set as follows:
1. Activate the menu "ALARM REPEAT TIME:"
2. Set the desired value using the arrow keys
3. Confirm the setting using NEXT.
9.5
Resetting the parameters
To restore all parameters to the pre-set standard, works:
1. Activate SET PARAMETERS TO DEFAULT.
2. Select the menu ARE YOU SURE? with ↵.
3. Press one of the buttons
for all parameters to be restored.
4. Press NEXT to confirm.
417101089_CDI01.doc
and
button.
and
or
to select from NO to YES,
- 55 -
and
button.
.
Rev.: 4-01/10