Herunterladen Inhalt Inhalt Diese Seite drucken

Omron VARISPEED E7 CIMR-E7Z Kurzanleitung Seite 21

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 25
Param-
eter
Name
Num-
ber
U3-09
to
Fifth last to tenth last fault
U3-14
U3-15
to
Accumulated time of fifth to tenth fault
U3-20
* The following faults are not recorded in the error log:
CPF00, 01, 02, 03, UV1, and UV2.
Digital Input Function Selections (H1-01 to H1-05)
3
Multi-step speed reference 1
4
Multi-step speed reference 2
Jog frequency command (higher priority than multi-
6
step speed reference)
F
Not used (Set when a terminal is not used)
14
Fault reset (Reset when turned ON)
19
PI control disable
External fault; Input mode: NO contact/NC contact,
20 to
2F
Detection mode: Normal/during operation
Digital Output Function Selections
(H2-01 and H2-02
During run 1 (ON: run command is ON or voltage is
0
being output)
Inverter operation ready; READY: After initialization or
6
no faults
F
Not used. (Set when the terminal is not used.)
10
Minor fault (Alarm) (ON: Alarm displayed)
1A
During reverse run (ON: During reverse run)
Motor overload (OL1, including OH3) pre-alarm (ON:
1F
90% or more of the detection level)
Description