Siemens SIPROTEC 5 Handbuch Seite 147

Kommunikationsprotokolle
Vorschau ausblenden Andere Handbücher für SIPROTEC 5:

Werbung

Cause of Transmission
(system-specific parameter, all configurations that are used are to be marked X)
One octet
Length of APDU
(system-specific parameter, specify the maximum length of the APDU per system)
The maximum length of APDU for both directions is 253. It is a fixed system parameter
Maximum length of APDU per system in control direction
Maximum length of APDU per system in monitor direction
Process Information in Monitor Direction
(station-specific parameter, mark each Type ID X if it is only used in the standard direction, R if only used in
the reverse direction, and B if used in both directions)
<2> := Single-point information with time tag
<4> :=Double-point information with time tag
<6> := Step position information with time tag
<8> := Bitstring of 32 bit with time tag
<9> := Measured value, normalized value
<10> := Measured value, normalized value with time tag
<11> := Measured value, scaled value
<12> := Measured value, scaled value with time tag
<14> := Measured value, short floating point value with time tag
<16> := Integrated totals with time tag
<17> := Event of protection equipment with time tag
<18> := Packed start events of protection equipment with time tag
<19> := Packed output circuit information of protection equipment with time tag
<20> := Packed single-point information with status change detection
<21> := Measured value, normalized value without quality descriptor
<33> := Bitstring of 32 bit with time tag CP56Time2a
<34> := Measured value, normalized value with time tag CP56Time2a
<35> := Measured value, scaled value with time tag CP56Time2a
<39> := Packed start events of protection equipment with time tag CP56Time2a
<40> := Packed output circuit information of protection equipment with time tag
CP56Time2a
The ASDUs of the set <2><4><6><8><10><12><14><16><17><18><19> are used.
Process Information in C ontrol Direction
<48> := Set point command, normalized value
<49> := Set point command, scaled value
<51> := Bitstring of 32 bit
<58> := Single command with time tag CP56Time 2a
SIPROTEC 5, Kommunikationsprotokolle, Handbuch
C53000-L1800-C055-2, Ausgabe 06.2016
IEC 60870-5-104
4.3 Interoperabilität
M_SP_TA_1
M_DP_TA_1
M_ST_TA_1
M_BO_TA_1
M_ME_NA_1
M_ME_TA_1
M_ME_NB_1
M_ME_TB_1
M_ME_TC_1
M_IT_TA_1
M_EP_TA_1
M_EP_TB_1
M_EP_TC_1
M_SP_NA_1
M_ME_ND_1
M_BO_TB_1
M_ME_TD_1
M_ME_TE_1
M_EP_TE_1
M_EP_TF_1
C_SE_NA_1
C_SE_NB_1
C_BO_NA_1
C_SC_TA_1
147