Herunterladen Inhalt Inhalt Diese Seite drucken

Output Values - Power One AURORA PVI-10.0-I-OUTD-400 Installations- Und Bedienungshandbuch

Photovoltaik-wechselrichter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Use and installation manual
(PVI-10.0/12.0-I-OUTD(-S)-400 Rev:1.3)
:
NOTE
If the photovoltaic field connected to the inverter supplies an
input current which is greater than the maximum usable value, the
inverter will not be damaged as long as the input voltage is within the permitted
range.
8.2

Output values

Description
Rated output power
Grid voltage maximum
operating range
Rated grid voltage
Grid frequency, maximum
range
Grid frequency, rated
Rated output current per
phase
Max. output current per
phase
Output over current
protection
Value
PVI-10.0-I
10000 W
from 326 Vrms to 480 Vrms phase-phase
from 188 Vrms to 263 Vrms phase-neutral
400 Vrms phase-phase
230 Vrms phase-neutral
47 / 63 Hz
14.5A
16A
20A
93
Page
Value
PVI-12.0-I
12000 W
50Hz
17.4A
18A
20A
97