Function Output A1
4. Parameter Description
Defines which variable is displayed on analog output 1 (terminal
X2.18).
Adjustment Range:
Resolution:
Factory setting:
Note:
ENTER-Parameter
Value Output Variable
0
Actual speed
1
Motor apparent current
2
Actual torque
3
DC-bus voltage
4
Speed reference (CP.6)
5
Control difference
(speed controller)
6
Set torque
During open-loop operation (CP.32 = 0) the analog
output A1 has no function with the values 2,5, and 6.
ANTRIEBSTECHNIK
0...6
1
2
Value Range when CP.19 = 1
^
-2 • n
... +2 • n
=
fn
fn
^
0 ... 2 • I
=
SN
^
-2 • M
... +2 • M
=
N
N
^
0 ... 1000 V
=
^
-2 • n
... +2 • n
=
fn
fn
^
-2 • n
... +2 • n
=
fn
fn
^
-2 • M
... +2 • M
=
N
N
n
: Rated-Rotating Field Speed
fn
M
: Rated Torque
N
I
: Rated-Motor Apparent Current
SN
GB
-10V ... +10V
0 ... +10V
-10V ... +10V
0 ... +10V
-10V ... +10V
-10V ... +10V
-10V ... +10V