Wiring of the control connections

4.7.1

Important notes

Stop!
The control card will be damaged if
ƒ
ƒ
Limit the voltage before switching on the drive controller:
ƒ
ƒ
For trouble-free operation, the control cables must be shielded:
ƒ
– For cables for digital inputs and outputs, connect the shield at both ends.
– For cables for analog inputs and outputs, only connect the shield at the drive
controller end.
– For lengths of 200 mm and more, use only shielded cables for analog and digital
inputs and outputs. Under 200 mm, unshielded but twisted cables may be used.
Installation material required from the scope of supply:
Description
Shield sheet
Screw M4 × 10 mm (DIN 7985)
Terminal strip, 4-pole
(only for variants V004 and V024)
Terminal strip, 7-pole
Terminal strip, 4-pole
EDKVS9332X DE/EN/FR 2.0
the voltage between X5/39 and PE or X6/7 and PE is greater than 50 V,
the voltage between voltage source and X6/7 is greater than 10 V (common
mode) in case of supply via external voltage source.
Connect X5/39, X6/2, X6/4 and X6/7 directly to PE or
use voltage-limiting components.
Electrical installation
Wiring of the control connections
Important notes
Use
Shield connection for control cables
Shield sheet fastening
Connection of safety relay K
at X11
SR
Connection of digital inputs and outputs at X5
Connection of analog inputs and outputs at X6
4
Amount
1
1
1
2
2