Electrical installation
Basic device in the power range 55 ... 75 kW
Mains connection, DC supply
4.6.2
Mains connection, DC supply
Note!
ƒ
ƒ
0
}
PE
+
Fig.4-20
166
If a mains filter or RFI filter is used and the cable length between mains/RFI
filter and drive controller exceeds 300 mm, install a shielded cable.
For DC-bus operation or DC supply, we recommend using shielded DC
cables.
1
2
PE
+UG
L1
L2
L3
3
Mains connection, DC supply for 55 ... 75 kW drive controller
PE stud
Connect PE cable with ring cable lug
Conductive surface
Shield clamp
Connect shield with a surface as large as possible to the control cabinet mounting plate and
fasten with shield clamp (shield clamp is not part of the scope of supply)
To improve the shield connection, also connect the shield to the PE stud
Mains and DC bus connection
L1, L2, L3: Connection of mains cable with ring cable lugs
+U
, -U
: Connection of cable for devices in DC-bus connection with ring cable lugs
G
G
L1, L2, L3
M10
+U , -U
30 Nm
G
G
PE
264 lb-in
-UG
9300vec127