Electrical installation
Basic devices in the power range 0.37 ... 11 kW
Mains connection, DC supply
Mains connection, DC supply
0
1
2
L1, L2, L3
+U , -U
G
Fig.4-3
140
L1
L2
L3 +UG -UG
PE
0.5...0.6 Nm
4.4...5.3 lb-in
G
Mains connection, DC supply for drive controllers 0.37 ... 11 kW
Mains cable
Shield sheet
Securely clamp mains cable shield with the lugs
Mains and DC bus connection
L1, L2, L3: Connection of mains cable
+U
, -U
: Connection of cable for devices in DC-bus connection
G
G
Cable cross-sections up to 4 mm
Cable cross-sections > 4 mm
2
: Use wire end ferrules for flexible cables
2
: Use pin-end connectors
9300std033
EDKVS9332X DE/EN/FR 2.0