1. General description
The CIM 25X can be used as an SMS interface for
control and monitoring of Grundfos products (e.g.
E-pumps and Hydro MPC booster systems) from a
mobile phone.
Using simple SMS messages, it is for instance
possible to start and stop the pump/system, change
the setpoint and get status of important pump/system
data and alarm and warning messages.
SMS messages which can be sent by the user and
interpreted by the CIM 25X, are called commands.
Command
Description
Four numerical characters between 0 and 9. It will be ignored if the access code has not
been enabled. Numerical characters in front of <command> will generally be ignored if
[access code]
the access code has not been enabled. A space character after [access code] is optional.
A legal command as explained in the following sections. If a parameter is entered after
the command, there must be one or more space characters between the command and
<command>
the parameter.
One or more legal parameters for the command in question. The use of symbolic
parameters is explained here:
<phone number>:
<access option>:
<access code>:
<alpha numeric string>:
[parameter,
parameter ...]
<APN string>:
<day of week>:
<hour of day>:
<installation name>:
<IP address>:
<port number>:
<setpoint>:
* The number of digits depends on the country.
There is no distinction between
Note
lowercase and uppercase letters in the
commands.
The general syntax of commands is:
[access code] <command> [parameter, parameter ...]
[ ] indicates a field which is only used in certain
cases.
< > indicates a mandatory field.
All texts sent to or from the CIM 25X are
Note
in English and cannot be changed.
Texts appearing in the display of the mobile phone
are written in the font Courier.
+XX YYY ZZZ ZZZZ (according to ITU-T E164). For local
calls, '+' and the country code XX are not required. *
LIST | CODE | BOTH | NONE.
See section 2. Configurating the CIM 25X.
Four numerical characters between 0 and 9 (4-digit code).
Max. 50 characters A-Z, a-z, 0-9.
Max. 64 characters A-Z, a-z, 0-9, '-' and '.'
Must not begin or end with '-' and '.'
ALL, MON, TUE, WED, THU, FRI, SAT, SUN.
OFF, 0, 1, 2, ... , 24 (0=24).
All printable characters except @ and ':'.
xxx.xxx.xxx.xxx; xxx = [000; 255].
1-65535. Default setting: Modbus = 502; GENIpro = 49152.
Decimal number with or without a decimal point.
5