Command
SMSALARM <ON | OFF>
SMSWARN <ON | OFF>
STATUSPROTECT <ON | OFF>
Description
With this configuration command, it is possible to enable or disable
the transmission of alarm messages from the product in the form of a
STATUS1 message to all numbers in the phone number list. For
further information about the STATUS1 message, see section
3. Status commands.
The CIM 25X will acknowledge the change with this message:
SMSALARM: changed to <ON | OFF>
Example of alarm message for a Hydro MPC booster system:
[Installation name]
ALARM APPEARED
Water shortage (214)
Setpoint 78 %
Act. setpoint: 4.2 bar
Act. value: 4.0 bar
Stopped due to alarm
If the function is enabled, a message will also be sent when the
cause of the alarm has disappeared and the product has returned to
normal state. The message content will be the same, the message
will, however, read:
ALARM DISAPPEARED.
To see the setting, use the command GSMSETTINGS.
Default setting: ON.
With this configuration command, it is possible to enable or disable
the transmission of warning messages from the product in the form
of a STATUS1 message to all numbers in the phone number list. For
further information about the STATUS1 message, see section
3. Status commands.
The CIM 25X will acknowledge the change with this message:
SMSWARN: changed to <ON | OFF>
Example of warning message for a Hydro MPC booster system:
[Installation name]
WARNING APPEARED
Feedback sensor signal fault (171)
Setpoint 78 %
Act. setpoint: 4.2 bar
Act. value: 4.0 bar
START from GSM
If the function is enabled, a message will also be sent when the
cause of the warning has disappeared and the product has returned
to normal state. The message content will be the same, the message
will, however, read:
WARNING DISAPPEARED.
To see the setting, use the command GSMSETTINGS.
Default setting: ON.
As default, access control does not prevent status commands from
being executed. Only unauthorised configuration and control
commands are blocked. If access control is to be applied for all
commands (status protection), this configuration command can be
used to activate status protection.
To see the setting, use the command GSMSETTINGS.
Default setting: OFF.