Herunterladen Diese Seite drucken

Grundfos CIM 25X SMS commands Montage- Und Betriebsanleitung Seite 96

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 146
Command
STATUS1/STATUS2
VERSION
BATTERY
NETWORK
16
Description
With these status commands, it is possible to get information from the CIM 25X
about the Grundfos product. The values measured are as reported from the
Grundfos product. The content of the message depends on the product type.
Example of STATUS1 message for a pump:
[Installation name]
Setpoint: 65 % of (0-10 bar)
Act. setpoint: 6.5 bar
Act. value: 5.2 bar
START from GSM
Control: Const. press.
Example of STATUS2 message for a pump:
[Installation name]
Head: 8.4 m
Flow: 24 m3/h
Power: 1830 W
Performance 79 %
Energy: 4570 kWh
Hours: 2568 h
With this status command, it is possible to get pieces of information, such as the
software version of the CIM 25X and the type of Grundfos product.
Example of reply:
[Installation name]
CIM 25X V01.00.00
Telit 07.03.101
Hydro MPC booster
IMEI: 3570220010091936
IMSI: 770008945629634
IMEI is the equipment identity number, and IMSI is the subscriber identity number.
With this status command, it is possible to get information about the battery status
if the CIM 25X is equipped with a battery (optional).
Example of reply:
[Installation name]
External voltage: Yes
Battery voltage: 3.5 V
Battery temp: 37 C
Battery charging: Yes
Charging suspended: No
Battery charging is suspended if the temperature is too high.
With this status command, it is possible to get information about the GSM network
and the network operator.
Example of reply:
[Installation name]
Operator: <operator>
Band: 900 MHz
GSM roaming: Yes
GPRS roaming: No
Power on: 1672:32 h

Werbung

loading