Grundfos CIM 25X SMS commands Montage- Und Betriebsanleitung Seite 90

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 146
Command
TIME <year>, <month>, <day>,
<hour>, <minute>
10
Description
Device OK will be replaced by an alarm/warning text if there is a fault
in the device. See section 3. Status commands.
To perform the function, the CIM 25X depends on time information
being available. The CIM 25X normally gets the time value from the
GSM network upon initialisation after a power cut. If this service is
not available in the network and the heartbeat function has been
activated, the CIM 25X will send this message:
NOTICE: Your GSM network does not support time
information. Please enter: "TIME yyyy, mm, dd, hh,
mm" for the heartbeat function to work.
Note: If the message is sent because the heartbeat function was
activated, it will only be sent to the phone number that activated the
function. If the message is sent because of missing time information
at initialisation, it will be sent to all numbers in the phone number list.
When the time value has been set either manually with the command
TIME or automatically from the network service, the internal real time
clock of the CIM 25X will work correctly as long as a power supply is
present.
To see the settings, use the command GSMSETTINGS.
Default setting: OFF.
If the GSM network does not support time information for
synchronising the internal real time clock of the CIM 25X, this
command can be used to supply the information. Once
synchronised, the internal clock will run as long as the CIM 25X is
powered or connected to its backup battery.
Parameters:
<year>:
2010-2100
<month>:
1-12
<day>:
1-31
<hour>:
0-23
<minute>:
0-59
If the setting has been done correctly, the CIM 25X will send this
message:
TIME: Time has been set to <year> <month> <day>
<hour>:<minute>
<month>: A three-letter truncation of month.
Example:
The command TIME 2010, 5, 6, 9, 30 results in this message:
TIME: Time has been set to 2010 May 6 09:30
If any of the parameters are outside their specified range or missing,
the CIM 25X will send this message:
TIME: Illegal or missing command parameter
The real time setting only influences the heartbeat function.
To see the value of the internal real time clock, use the command
GSMSETTINGS.