4. Control commands
4.1 CIM 25X
Command
Description
Resets GSM data counters. The CIM 25X will acknowledge the change with this
message:
RESETGSM
RESETGSM: GSM data counters reset
Resets GPRS data counters. The CIM 25X will acknowledge the change with this
message:
RESETGPRS
RESETGPRS: GPRS data counters reset
4.2 Grundfos product
By means of the control commands in the table
below, it is possible to set the Grundfos product to
run in the desired control mode and operating mode
and to change the setpoint. The CIM 25X will
acknowledge the change by sending a status1
message to the mobile phone from which the
command was sent.
Changing of control mode, operating mode or
setpoint for a pump will automatically set the pump to
remote-controlled operation. These settings will be
saved in the CIM 25X module in case of power cuts.
They can also be changed via a GSM call-up
connection or a GPRS connection. The latest
change of settings will apply. Changes via GSM call-
up connection or GPRS connection, however, are
not saved in the CIM 25X in case of power cuts.
Command
RESETALARM
REMOTE
LOCAL
START
STOP
MIN
MAX
Description
Resets an alarm or a warning in the Grundfos product if
the fault no longer exists. The product will try to restart.
Sets the Grundfos product to remote-controlled operation.
-
-
(The Grundfos product is controlled via the CIM 25X.)
Sets the Grundfos product to locally controlled operation.
(The setpoint, operating mode and control mode can be
-
-
changed on the product or by means of a Grundfos R100
remote control.)
Starts the Grundfos product.
-
Stops the Grundfos product.
-
Changes the operating mode of the Grundfos product to
-
-
-
Min. It will run according to the min. curve.
Changes the operating mode of the Grundfos product to
-
-
Max. It will run according to the max. curve.
Note: The commands depend on the Grundfos
product. If the command is not supported by the
product, the product will ignore the command, and
the CIM 25X will send this message:
<command>: Command not supported by
connected device type
Note: The commands are all subject to access
control if another access option than NONE has
been selected.
Note: Control of Hydro MPC via CIM 25X requires
this setting via the control panel of the CU 351.
Settings > Secondary functions > Control source.
Select From bus. For further information, see the
installation and operating instructions for Hydro MPC
on WebCAPS.