Command
SETPOINT <value>
CONSTCURVE
CONSTPRESS
●*
PROPPRESS
AUTOADAPT
ALARMSIM
<code>
WARNSIM <code>
* Only TPE 2000.
** Only MAGNA.
Example 1
The CIM 25X has been configured to access option
CODE, and the access code has been set to "8977".
An alarm can be reset with this command:
8977 RESETALARM
Example 2
The number of your mobile phone is in the phone
number list of the CIM 25X, and the access option is
BOTH (default setting). The setpoint can be changed
to 4.5 m with this command:
SETPOINT 4.5
Note that the unit of the setpoint is not to be written
as a part of the command parameter, as it is
implicitly given by the scaling unit of the feedback
value.
20
-
-
-
-
-
-
-
-
-
-
-
-
●**
-
-
-
-
-
●**
-
-
-
Description
Sends a new setpoint value to the product. If the setpoint
is outside the permissible range, it will automatically be
changed to the nearest value within the range.
Due to the limited scaling range and the resolution, the
resultant setpoint may deviate from the one sent to the
product.
Closed loop
The setpoint is specified as a decimal point value scaled in
the same unit as the feedback sensor. The command
STATUS1 provides information about the sensor scaling.
Note: UPE and MAGNA pumps always use [m].
Units on the MPC display can differ from "unit" if other
units than standard SI units have been selected for
sensors.
Open loop
The setpoint is specified as a decimal point value scaled
in %.
This command sets the Grundfos product to control mode
Constant curve.
This command sets the Grundfos product to control mode
Constant pressure.
This command sets the Grundfos product to control mode
Proportional pressure.
This command sets the Grundfos product to control mode
AUTO
.
ADAPT
This command makes the Grundfos product simulate an
alarm with an event code. If the product supports the alarm
selected and SMSALARM is set to ON, it will react
accordingly for instance by sending an alarm message.
This command makes the Grundfos product simulate a
warning with an event code. If the product supports the
warning selected and SMSWARN is set to ON, it will react
accordingly for instance by sending a warning message.