Command
SETGPRS <parameters>
14
Description
It is possible to configure the GPRS connection with this single
multiparameter command.
Parameters:
<APN>:
APN string or IP address
<Modbus port>:
1-65535
<GENIpro port>:
1-65535
<user name>:
alpha numeric string
<password>:
alpha numeric string
<authentication>: NORMAL | SECURE
<connection>:
SERVER | CLIENT | DISABLED
<GPRS roaming>: ON | OFF
Example 1:
SETGPRS Grundfos.dk2.tdc,502,49152,Grundfos,4321,
NORMAL,SERVER,OFF
Example 2:
SETGPRS Grundfos.dk2.tdc,502,49152,,,NORMAL
In the second example some parameters have been omitted in the
middle and at the end of the parameter string.
The CIM 25X acknowledges the change with the same message as
for the status command GPRSSETTINGS.