PMX command set (API)
434
busbits (p6) will be used to define the state of a digital
output.
p6: binary mask for the fieldbusbits which is ANDed with
the 32 fieldbusbits. If result is >0 (true) this digital output
will be set. A mask with more than one bit set is possible
too. Value range: 0,1,2,3...(2^321)
p7: enable for digital inputs (ON=1, OFF=0). If enabled
the status of the 16 digital inputs with the mask for the
digital inputs (p8) will be used to define the state of a di
gital output.
p8: binary mask for the digital inputs which is ANDed with
the 16 digital inputs. If result is >0 (true) this digital output
will be set. A mask with more than one bit set is possible
too. Value range: 0,1,2,3...(2^161)
p9: enable for parametersetnumber (ON=1, OFF=0). If
enabled the parametersetnumber with the mask for the
parametersetnumber (p10) will be used to define the
state of a digital output.
p10: binary mask for the parametersetnumber which is
ANDed with the currently active parametersetnumber. If
result is >0 (true) this digital output will be set. A mask
with more than one bit set is possible too. Value range:
0,1,2,3...(2^321)
p11: enable for calculatedchannelbits (ON=1, OFF=0). If
enabled the status of the 32 bit word which can be
defined by one or more calculatedchannel(s) in combina
tion with the mask for the calculated channels (p12) will
be used to define the state of a digital output.
p12: binary mask for the calculatedchannels which is
ANDed with the 32 calculatedchannel bits. If result is >0
(true) this digital output will be set. A mask with more
than one bit set is possible too. Value range:
0,1,2,3...(2^321)
A3257-5.1 HBM: public
PMX