Herunterladen Diese Seite drucken

HBM PMX Bedienungsanleitung Seite 135

Vorschau ausblenden Andere Handbücher für PMX:

Werbung

PMX
10.6 PMX startup behavior
Important
PMX initialization takes a few seconds. A self-test of all
the modules is run during this time. All the LEDs flash to
indicate this status. Once the self-test has been
completed, you can read the status of each component
from the relevant status LED (see Chapter 8.2.3 to 8.2.5).
S When the PMX is switched on, the digital and analog
outputs are set to 0 V.
S When the system powers up, the analog outputs are
set to 0 V.
S After power-up, the configured and valid outputs are
set to -10 ... + 10 V.
S Invalid (unconfigured) outputs jump to 0 V (safe
value).
If an output becomes invalid during operation, it will
also jump to 0 V.
S The safe value can be set to any other value, but its
default setting is 0 V.
A3257-5.1 HBM: public
Startup
133