Herunterladen Diese Seite drucken

Balluff BFD 3SAP-19N000-U01-LA2-C Serie Konfigurationsanleitung Seite 165

Ultraschall-sensoren

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BFD 3SAP-19N000-U01-LA2-C_ _ _ _ _
Ultrasonic sensors
7
System Functions (continued)
7.2
Diagnosis Suppression
7.2.1
Description
Diagnosis suppression is used to suppress diagnosis
messages from the device. There are two possibilities here:
Diagnosis suppression level that permits a general
suppression of messages of a certain level (message,
warning, error).
Event-code suppression of up to 5 events as a list or
via a teach-in.
7.2.2
ISDU
Name
Diagnosis Level Configuration
Event Code Suppression
Event Code Suppression
Event Code Suppression
Teach-in
Event Code Suppression
Delete
Tab. 7-5:
Diagnosis suppression – ISDU
7.2.3
Diagnosis Level Configuration
This parameter offers the possibility to select an output
level for events.
This index is part of the data management and is stored in
non-volatile memory.
Value
Diagnosis Level
0
All events
1
Warnings and errors
2
Error
3
No events
Tab. 7-6:
Diagnosis suppression – Diagnosis level configuration
www.balluff.com
Index
Subindex Access
0x0070 (112)
0
0x0071 (113)
0
1...5
0x0072 (114)
0
0x0073 (115)
0
Descriptions
All diagnosis messages are reported (default setting).
All warnings and errors are reported – messages are suppressed.
Only events of type error are reported.
All diagnosis messages from the device are suppressed.
Length
Data Type
R/W
1 byte
UINT8(ENUM)
R/W
10 bytes
R/W
2 bytes
UINT16
W
2 bytes
UINT16
W
2 bytes
UINT16
Data Storage
Default
Yes
0
Yes
No
0
n/a
n/a
english
73

Werbung

loading