BFD 3SAP-19N000-U01-LA2-C_ _ _ _ _
Ultrasonic sensors
6
Secondary Device Functions (continued)
6.8.5
System Commands
Command Value Device Action
0x81 (129)
Application Reset – Resets the
Voltage Monitoring Detection Time
Duration with ISDU-index 0x2200 to
the default value 10.
0x82 (130)
Restore Factory Settings – Resets
the Voltage Monitoring Detection
Time Duration with ISDU-index
0x2200 to the default value 10.
Tab. 6-42: Voltage and current monitoring – System Commands
For an overview of all System Commands, see section 3.5
on page 21.
6.8.6
Events
Event Code
Event Type
0x5110
Warning
(20752)
0x5111
Warning
(20753)
0x8D0B
Warning
(36107)
0x8D0D
Warning
(36109)
0x8D15
Warning
(36117)
Tab. 6-43: Voltage and current monitoring – Events
68
english
Event – Description – Remedy
Primary supply voltage exceeded
► Check for deviations in the supply.
Primary supply voltage below minimum value
► Check for deviations in the supply.
Overload or short circuit at pin 2
► Check wiring.
Incorrect load/cable breakage, analog current output pin 2
► Check wiring or connected devices.
Overload at pin 2
► Check wiring.
Device Status
2 – Out-of-Specification
2 – Out-of-Specification
2 – Out-of-Specification
2 – Out-of-Specification
2 – Out-of-Specification