Balluff BFD 3SAP-19N000-U01-LA2-C Serie Konfigurationsanleitung Seite 114

Ultraschall-sensoren

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BFD 3SAP-19N000-U01-LA2-C_ _ _ _ _
Ultrasonic sensors
3
Overview of IO-Link Data and Functions (continued)
3.6
Events
Event Code
Event Type
0x1850
Notification
(6224)
0x1851
Notification
(6225)
0x1852
Warning
(6226)
0x4000
Error
(16384)
0x4210
Warning
(16912)
0x4220
Warning
(16928)
0x5110
Warning
(20752)
0x5111
Warning
(20753)
0x8CFF
Warning
(36095)
0x8D00
Warning
(36096)
0x8D01
Warning
(36097)
0x8D02
Warning
(36098)
0x8D03
Warning
(36099)
0x8D04
Warning
(36100)
0x8D05
Warning
(36101)
0x8D07
Warning
(36103)
0x8D08
Warning
(36104)
0x8D09
Warning
(36105)
0x8D0B
Warning
(36107)
0x8D0D
Warning
(36109)
22
english
Event – Description – Remedy
Process data profile selection cannot be used –
default value is used.
Process Data Update Timeout – For information
purposes only.
Multiple Process Data Update Timeout – For
information purposes only.
Temperature Fault – Overload – The device is
operated outside of the device-specific temperature
limits. Risk of device damage.
Device Temperature Overrun – Clear Heat Of Source
– Risk of device damage. The device is too hot.
► Remove heat source, provide the device with
heat insulation if necessary.
Device Temperature Underrun – Insulate Device –
Risk of device damage. The device is too cold.
► Insulate the device.
Primary supply voltage exceeded
► Check for deviations in the supply.
Primary supply voltage below minimum value
► Check for deviations in the supply.
Low signal quality level
The measurement value is below the measurement
range.
Accuracy cannot be guaranteed.
The measurement value is above the measurement
range.
Accuracy cannot be guaranteed.
The measurement value is below the detection
range; no measurement value can be determined.
► Check application.
The measurement value is above the detection
range; no measurement value can be determined.
► Check application.
No measurement value can be determined.
► Check application.
Measurement error/redundancy check failed.
► Check application.
The calculation of the basic statistics was stopped
automatically to avoid a buffer overflow.
Speed value is below the limit.
Speed value is above the limit.
Overload or short circuit at pin 2
► Check wiring.
Incorrect load/cable breakage, analog current output
pin 2
► Check wiring or connected devices.
Device Status
0 – Device is operating properly.
0 – Device is operating properly.
0 – Device is operating properly.
4 – Failure
2 – Out-of-Specification
2 – Out-of-Specification
2 – Out-of-Specification
2 – Out-of-Specification
0 – Device is operating properly.
2 – Out of Specification
2 – Out of Specification
2 – Out of Specification
2 – Out of Specification
2 – Out of Specification
2 – Out of Specification
0 – Device is operating properly.
0 – Device is operating properly.
0 – Device is operating properly.
2 – Out-of-Specification
2 – Out-of-Specification