Balluff BFD 3SAP-19N000-U01-LA2-C Serie Konfigurationsanleitung Seite 121

Ultraschall-sensoren

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BFD 3SAP-19N000-U01-LA2-C_ _ _ _ _
Ultrasonic sensors
5
Primary Device Functions (continued)
Setpoint 1 must be greater than setpoint 2.
The distance between the setpoints must be greater
than or equal to the minimum hysteresis.
Due to the requirements listed above, it may be
necessary to vary the order of the setpoints for a
successful teach-in.
An active teach process is indicated by illumination of the
red LED. If the red LED flashes, the currently pending
measurement value is outside of the validity range (IO-Link
process) or a manual teach was not possible.
Single-Value Teach
With Single-Value Teach, the switching point (setpoint) is
defined via a teach point. Moreover, this is a static process,
i.e., the measurement value is constant during the teach
phase. The teach process is performed independently for
each switching point in Two-Point Mode or Window Mode.
Low
Workflow:
1. Teach SP1
Fig. 5-6:
Single Value Teach in Single Point Mode
Low
SP2
Workflow:
1. Teach SP2
2. Teach SP1
Fig. 5-7:
Single-Value Teach in Two-Point Mode
Two-Value Teach
With Two-Value Teach, the switching point (setpoint) is
defined via two teach points. The average value of the two
teach points defines the setpoint. This is a static process
as well, i.e., each teach point is defined statically. The
teach process can be performed independently for each
switching point in Two-Point Mode or Window Mode. The
teach process is concluded with the Apply command; this
is only possible if each of the two teach points has been
taught. Alternatively, the teach process can be interrupted
with a Cancel command. All incomplete teach point pairs
are thereby lost.
www.balluff.com
High
SP1
Measured value
High
SP1
Measured
value
Low
Workflow:
1. Teach SP1 TP1
2. Teach SP1 TP2
3. Teach Apply
Fig. 5-8:
Two Value Teach in Single Point Mode
Low
SP2
Workflow:
1. Teach SP2 TP1
2. Teach SP2 TP2
3. Teach Apply (optional)
4. Teach SP1 TP1
5. Teach SP1 TP2
6. Teach Apply
TP1
TP2
Fig. 5-9:
Two-Value Teach-In Two-Point Mode
Dynamic Teach (Smart Sensor Profile Spec.)
With this process, no static teach points are recorded,
unlike with the previous methods; rather, multiple
measurement values are recorded over a defined period of
time. Measurement value acquisition is started with the
Dynamic Teach SP1 Start system command and ended
with Dynamic Teach SP1 Stop. If all recorded
measurement values were in the valid detection range, the
switching point calculation is started. For this purpose, the
minimum and maximum values are determined. The
average value of these two extrema is used to form the
new switching point (setpoint). The maximum acquisition
time is 5 minutes. After 5 minutes without a Stop
command, the event 0x8DC0 Teach Timeout is set.
Low
Workflow:
1. Dynamic Teach SP1 Start
2. Dynamic Teach SP1 Stop
Fig. 5-10:
Dynamic Teach in Single-Point Mode
High
SP1
Measured
value
TP1 TP2
High
SP1
Measured
value
TP1 TP2
High
SP1
Measured
value
Recorded measured values
english
29