Error table

Classification No.
-
0
System
E004
errors
E005
E006
E007
Pump errors
E010
Motor errors E020
E021
E023
E025
E026
Electronic
E030
modules
errors
E031
E032
E033
E035
Communica-
E050
tion errors
116
Fault
Cause
No fault
Undervoltage
Mains overloaded
overvoltage
Mains voltage too high
2-phase operation
Missing phase*
Warning! Generator
The flow is driving the
operation
pump impeller; electrical
(flow in flow direction)
current is being fed back
to the mains
Blocking
Shaft is mechanically
Blocked
Excess winding tem-
Motor overloaded
perature
Motor ventilation limited Provide unobstructed air
Water temperature too
high
Motor overload
Duty point outside of
duty chart*
Deposits in the pump
Short circuit/earth
Motor or electronic mod-
leakage
ule defective
Faulty contact
Electronic module has no
contact to motor
Winding interrupted
Motor faulty
WSK or PTC inter-
Motor faulty
rupted
Excess temperature
Limited air supply to the
Electronic module
heat sink of the elec-
tronic module
Excess hybrid/power
Ambient temperature too
section temperature
high
Intermediate circuit
Voltage fluctuations in
undervoltage
the mains
Intermediate circuit
Voltage fluctuations in
overvoltage
the mains
DP/MP: multiple
Multiple instances of
instances of same
same identity
identity
BMS communication
Bus communication
time-out
interrupted or timed out
Broken cable
Remedy
Check electrical installation
Check electrical installation
Check electrical installation
Check the setting, check sys-
tem for proper operation
Caution! Prolonged operation
can cause damage to the elec-
tronic module
If the blocking has not been
removed after 10 seconds, the
pump switches off.
Check shaft for ease of move-
ment
Request customer service
Allow motor to cool down
Check settings
Check/correct the duty point
access
Lower water temperature
Check/correct the duty point
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Provide unobstructed air
access
Improve room ventilation
Check electrical installation
Check electrical installation
Reallocate master and/or slave
(see Chapter 9.2 on page 107)
Check cable connection to
building automation
Error type
HV
AC
C
A
C
A
C
A
F
F
A
A
B
A
B
A
A
A
A
A
B
A
B
A
B
A
F
D
F
D
E
E
F
F
WILO SE 08/2022