Faults, causes and remedies
14.1
Mechanical faults without error
messages
14.2

Diagnostics help

Installation instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
Faults, causes and remedies
WARNING
Have faults remedied by qualified personnel only! Observe safety in-
structions.
In the event of faults, fault management only provides feasible pump outputs and
functionalities.
Any occurred faults are permanently checked and, if mechanically possible, emergency
operation or control mode are activated.
Flawless pump operation is only resumed once the fault cause no longer applies. Ex-
ample: The electronic module is again cooled down.
Configuration warnings indicate that an incomplete or wrong configuration is prevent-
ing execution of a desired function.
NOTICE
If the pump behaves incorrectly, check that the analogue and digital inputs are con-
figured correctly.
For details, see the detailed instructions at www.wilo.com
If the malfunction cannot be rectified, consult a specialist technician or the nearest
Wilo customer service or representative location.
Faults
Causes
Pump does not start or
Cable terminal loose.
stops working.
Pump does not start or
Fuse protection defect.
stops working.
Pump runs at reduced
Stop valve on the pressure
performance.
side throttled.
Air in the suction line.
Pump runs at reduced
performance.
Cavitation due to insuffi-
cient suction pressure.
Pump makes noises.
Motor has bearing damage.
Pump makes noises.
Table 18: Mechanical faults
In order to support fault analysis, the pump provides additional help apart from fault
notifications:
Diagnostics help is used for diagnosis and maintenance of electronics and interfaces.
Apart from hydraulic and electrical overviews, information about interfaces, device in-
formation and manufacturer's contact data are provided.
In the "Diagnostics and measured values" menu
1.
"Diagnostics help".
For details, see the detailed instructions at www.wilo.com
Remedy
Fuse protection defect.
Check fuses; replace faulty
fuses.
Slowly open the stop valve.
Eliminate leakage at flanges.
Vent pump. In case of visible
leakage, replace the mechan-
ical seal.
Increase the suction pressure.
Observe the minimum inlet
pressure at the suction port.
Check slide valve and filter on
the suction side and clean if
need be.
Have the pump checked by
Wilo customer service or a spe-
cialised service centre and re-
paired if necessary.