Herunterladen Inhalt Inhalt Diese Seite drucken

Error Messages - Wilo Para MAXO Einbau- Und Betriebsanleitung

Vorschau ausblenden Andere Handbücher für Para MAXO:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Faults, causes and remedies
Manual deblocking
ƒ
Press and hold the operating button for 4 seconds. The deblocking function is initi-
ated and lasts for a maximum of 30 minutes. The following animation appears during
this process:
NOTICE
After successful deblocking, the LED display shows the previously set values of
the pump.
ƒ
Interrupt the power supply and switch it on again.
If a fault cannot be repaired, contact a qualified specialist or the Wilo customer ser-
vice.
10.2

Error messages

Faults
Final fault
Rotor blocked (final).
LED: lights up red
SSM relay: opened
PWM out: 95 %
LIN: final fault 03
Modbus: final fault 10
Motor defective
LED: lights up red
SSM relay: opened
PWM out: 95 %
LIN: final fault 01
Modbus: final fault 23
Installation and operating instructions Wilo-Para MAXO/-G/-R/-Z
Version F01 and F02 (equipped with an operating button):
All other versions:
Causes
Pump off.
Rotor still blocks after deblocking
routine.
Pump off.
Motor faulty.
Remedies
Activate manual restart or contact
customer service.
Contact customer service.
en
95

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Para maxo-gPara maxo-rPara maxo-z

Inhaltsverzeichnis