fire mode

15. FIRE MODE
The SL6+ system can be used as a fire depart-
ment intercom system. Depending on the
configuration, up to 6 bus units
can be used as a fire intercom system. Fire
mode is started by activating an input on the
main intercom station.

Configuration

To configure the dialling unit in fire mode, use
parameter *73* (cf. parameter list).
Set input 1 to fire mode: *73*14#
Set input 2 to fire mode: *73*24# (default)
Using SL-Pro software, select which other bus
units to include in the fire mode.

Operation

Activation of fire mode (when the input defined
above is activated) will result in the following:
A siren signal sounds in the speaker of the
dialling unit. Press the reset button to stop the
siren sound. The voice announcement for the
fire mode (parameter *57*) is played. When the
fire mode is activated, the stations can only be
operated as intercom system and no emergency
calls are possible.
88

Voice communication

Bus device in the cabin: Microphone and
speaker are both active.
Other stations: The emergency button
becomes a push-to-talk button (press to talk,
release to listen).
A short beep is emitted when the button is
pressed and released.
In fire mode, you can use the machine room
telephone to participate in the conversation
via the dialling unit.
The yellow pictogram lights up when the fire
mode is activated.
The green pictogram lights up when the
speaking mode is activated and turns off
when listening.
Fire mode is terminated by deactivating the
input (1 or 2) on the main intercom station
configured for fire mode.