15. FIRE MODE
The SL6+ system can be used as a fire depart-
ment intercom system. Depending on the
configuration, up to 6 bus units
can be used as a fire intercom system. Fire
mode is started by activating an input on the
main intercom station.
Configuration
To configure the dialling unit in fire mode, use
parameter *73* (cf. parameter list).
▸
Set input 1 to fire mode: *73*14#
▸
Set input 2 to fire mode: *73*24# (default)
▸
Using SL-Pro software, select which other bus
units to include in the fire mode.
Operation
Activation of fire mode (when the input defined
above is activated) will result in the following:
A siren signal sounds in the speaker of the
dialling unit. Press the reset button to stop the
siren sound. The voice announcement for the
fire mode (parameter *57*) is played. When the
fire mode is activated, the stations can only be
operated as intercom system and no emergency
calls are possible.
88
Voice communication
▸
Bus device in the cabin: Microphone and
speaker are both active.
▸
Other stations: The emergency button
becomes a push-to-talk button (press to talk,
release to listen).
▸
A short beep is emitted when the button is
pressed and released.
▸
In fire mode, you can use the machine room
telephone to participate in the conversation
via the dialling unit.
▸
The yellow pictogram lights up when the fire
mode is activated.
▸
The green pictogram lights up when the
speaking mode is activated and turns off
when listening.
▸
Fire mode is terminated by deactivating the
input (1 or 2) on the main intercom station
configured for fire mode.