*74*
1 or 2;
0 or 1 #
*88*
1 or 2;
0 to 7 #
*89*
1 to 6;
0 or 1 #
*90*
1 to 6;
0 or 1 #
Type of inputs 1 and 2
Outputs (relays 1 and 2)
Bus unit settings
Button type on bus unit
Horn on bus unit
configurAtion StepS
The first digit indicates whether input
1 or 2 is defined. The second digit sets
the selected input to normally open
(NO) for 0 or to normally closed (NC)
for 1.
The first digit selects the output (relay
1 or 2). The second digit selects the
desired function (cf. chapter "Relay"):
0 = Emergency call state (default for
relay 1)
1 = Battery failure (default for relay 2)
2 = Pictograms (relay 1 = yellow,
relay 2 = green)
3 = Manual activation via DTMF tone
(relay 1 = 8, relay 2 = 9)
4 = Manual reset
5 = Failure of the emergency call
6 = System error (for shutdown)
7 = Emergency horn (potential-free
alternative to horn output)
This parameter sets the type of the
button input of the bus units. The first
digit determines which bus unit is set
and the second digit sets the input
to normally open (NO) for 0 and to
normally closed (NC) for 1. By default,
all bus units are set to normally open
(NO).
This parameter sets the type of the
horn output of the bus units. The first
digit determines which bus unit is set
and the second digit sets the output
to normally open (NO) for 0 and to
normally closed (NC) for 1. By default,
all bus units are set to normally open
(NO).
Behnke AT6 manual
81