Status
LED
Backwater in
Backwater in
Temperature
flushing swit-
ched off during
Volume flus-
hing switched
off during
Pt 1000 value
Pt 1000 value
Leak on sensor
clock data
inconsistent
Flow detected
with valve
„No flow de-
tected despite
open valve"
166 / 259 – K410068602008-00 / 09.2020 – © www.kemper-olpe.de
Error description and error handling
Error description / Error handling
Error
Possible cause
Drain is clogged or can-
not accept the flushing
drain
volume.
Float switch on the drain
drain
has a cable break.
Medium did not reach the
switch-off temperature in
the set time.
runtime
Set volume not reached.
runtime
Sensor defective / No
too high
sensor available
Sensor defective / No
too low
sensor available
Pipe failure, moisture on
the sensor
Real-time
Data in the clock are not
consistent
Flow is detected by the
flow measurement valve
closed
when the valve is closed.
No flow is detected du-
ring a flushing process.
Measure
General error
Check the drain
channel, channel
acceptance capacity.
Replace cable /
switch.
Check the installa-
tion setup and the
maximum flushing
time.
Check the installa-
tion setup and the
maximum flushing
time.
Replace sensor /
Check inputs on the
MASTER.
Replace sensor /
Check inputs on the
MASTER.
Check the local area
and remove the
moisture.
Check the time &
date and adjust if
necessary. Check
battery/replace if
applicable.
Check the function
of the flushing valve.
Check the flushing
line and the flushing
valve.
Effect
Error message!
Defective control will be
completely blocked.
Error message!
Defective control will be
completely blocked.
Error message!
Temperature operating
mode is blocked in the
defective control.
Error message!
Volume operating mode
is blocked in the defective
control.
Error message!
Temperature flushing
operating mode is blocked
in the defective control.
Error message!
Temperature flushing
operating mode is blocked
in the defective control.
The safety valve is blo-
cking the system.
All time-based services
are running on incorrect
time/date.
Error message! The invol-
ved valve will be blocked.
Error message! The invol-
ved valve will be blocked.