Condition Monitoring Sensor
6
IO-Link interface (continued)
6.2.2

Device configuration

The event detection of the BCM is controlled in index
0x005E (94). The subindex 0x01 (1) configures the waiting
time in seconds during which no events are detected for all
modules.
The status bits are kept True at least as long as they are
configured in the subindex 0x02 (2).
Index
Sub index
Access
GENERAL ALARM CONFIGURATION
0x005E
0x01 (1)
Read/Write
(94)
0x02 (2)
Read/Write
PROCESS DATA PROFILE
0x2000
0x00 (0)
Read/Write
(8192)
0x2001
0x01 (1)
Read/Write
(8193)
0x02 (2)
Read/Write
0x03 (3)
Read/Write
0x04 (4)
Read/Write
PING
0x200A
0x00 (0)
Read/Write
(8202)
0x200B
0x00 (0)
Read only
(8203)
Tab. 6-3:
Device configuration
20
english
There are ready-made profiles available for the process
data of the sensor (index 0x2000 (8192)). The user-defined
profile (index 0x2001 (8193)) can be tailored precisely to
the specific application.
For the ping function, a timeout can be configured in index
0x200A (8202) subindex 0x00 (0), and the current status of
this function can be retrieved in index 0x200B (8203)
subindex 0x00 (0).
Description
DELAY START MONITORING –
Time in seconds since the last
startup in which no alarms are
evaluated.
STATUS BIT HOLD UP TIME – Time
in milliseconds in which a status bit
at the very least remains set,
regardless of whether the threshold
is still exceeded or not.
PROCESS DATA PROFILE –
Selected process data profile (see
Process data profile (PROCESS
DATA PROFILE) on page 21)
Slot 1 – Configuration of the first
slot of the user-defined process
data profile
Slot 2 – Configuration of the second
slot of the user-defined process
data profile
Slot 3 – Configuration of the third
slot of the user-defined process
data profile
Slot 4 – Configuration of the fourth
slot of the user-defined process
data profile
PING TIMEOUT – Time in minutes
for which the BCM activates the
ping feature via the corresponding
command
PING STATUS – Indicates whether
the ping feature is currently active
(True) or not (False)
Data type
Value range
uint16
0...65535 [s]
uint16
0...65535 [ms]
uint8
see
Process data
profile (PRO-
CESS DATA
PROFILE) on
page 21
See
User-defined process data
profile (CUSTOM PROCESS
DATA PROFILE
CONFIGURATION) on
page 21
uint16
1...60 [min]
bool
Default value
0 [s]
0 [ms]
1
2 [min]