BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
6
IO-Link interface (continued)
Time window of the vibration module
(TIME WINDOW VIBRATION)
Index 0x2102 (8450) can be used to select the time
window for the vibration module over which the statistical
evaluation of the signal takes place. The time window,
depending on the selected value, is entered in Tab. 6-16.
When choosing the time window, note that the
frequency of the signal must not be less than a
minimum frequency as defined in Tab. 3-3 on
page 11. When setting the time window and
when setting the lower band limit of the
bandpass filter, invalid values are rejected with
error code 0x8040 (32832) or 0x8041 (32833).
The bandpass filter can be configured using
index 0x2103 (8451) (see page 28).
Value
0x00 (0)
0x01 (1)
0x02 (2)
0x03 (3)
0x04 (4)
This time window is not compatible with the default value for the lower
1)
band limit. Observe note!
Tab. 6-16: Time window configuration
Severity zone (SEVERITY ZONE)
The variable stored in index 0x2117 (8471) subindex 0x00
(0) indicates the current degree of severity of vibration. The
boundaries of the severity zones can be configured in
index 0x2108 (8456).
Variable content
0b00
0b01
0b10
0b11
Tab. 6-17: Severity zone
www.balluff.com
Time window
20 ms
1)
100 ms
1)
250 ms
500 ms
1000 ms
Severity zone
Zone A
Zone B
Zone C
Zone D
english
37