Condition monitoring sensor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
6
IO-Link interface (continued)
Process data profile (PROCESS DATA PROFILE)
Index 0x2000 (8192) subindex 0x00 (0) defines the
process data profile. The profiles are explained in Section
Process data from page 38.
Value of
Selected profile
PROCESS
DATA PROFILE
1
VIBRATION VELOCITY
2
VIBRATION VELOCITY PEAK-TO-
PEAK
3
VIBRATION ACCELERATION
4
VIBRATION ACCELERATION PEAK-
TO-PEAK
5
ENVIRONMENTAL
8
CUSTOM PROCESS DATA
PROFILE
only for the BCM R15E-002-DI00-_ _ , _-S4
1)
The CUSTOM PROCESS DATA PROFILE can be configured in
2)
index 0x2001 (8193).
Tab. 6-4:
Process data profiles
www.balluff.com
1)
2)
User-defined process data profile (CUSTOM
PROCESS DATA PROFILE CONFIGURATION)
Index 0x2001 (8193) defines the user-defined process data
profile: each slot is configured in a subindex. Slot 1 is
configured in the first subindex, slot 2 is configured in the
second, slot 3 in the third and slot 4 in the fourth subindex.
The subindices 0x01 (1) to 0x04 (4) can be identically
configured according to Tab. 6-5.
Byte 0
Byte 1
MSB index
LSB index
Tab. 6-5:
Byte meaning of the subindices from CUSTOM PROCESS
DATA PROFILE CONFIGURATION
This enables the analysis variables that are available in the
service data to be applied to the process data. The status
bits are held in place in a 5th slot.
All possible values for the process data are listed in
Tab. 6-6 on page 22.
Example:
If the contact temperature is to be applied to slot 2 and the
v-RMS magnitude is to be applied to slot 4, the byte
sequence 0x20 (32) 0x31 (49) 0x01 (1) 0x00 (0) for the
contact temperature must be written to subindex 0x02 (2)
and the byte sequence 0x21 (33) 0x14 (20) 0x04 (4) 0x00
(0) for the v-RMS magnitude must be written to subindex
0x04 (4). These values can both be taken from Tab. 6-6 as
well as determined from the indices of the service data.
The contact temperature is in index 0x2031 (8241),
subindex 0x01 (1). Therefore, bytes 0x20 (32) 0x31 (49)
0x01 (1) 0x00 (0) must be written to the corresponding
subindex.
Contact temperature (CONTACT TEMPERATURE)
0x2031 (8241)
Index
Byte 0:
Byte 1:
0x20 (32)
0x31 (49)
Write in user-defined process data profile
CUSTOM PROCESS DATA PROFILE CONFIGURATION
Slot
Index
1
2
0x2001
(8193)
3
4
Fig. 6-1:
Defining the contact temperature in any slot in the user-
defined process data profile
Byte 2
Byte 3
Sub index
0x00 (0)
0x01 (1)
Sub index
Byte 2:
Byte 3:
0x01 (1)
0x00 (0)
Sub index
0x01 (1)
0x02 (2)
0x03 (3)
0x04 (4)
english
21