Herunterladen Inhalt Inhalt Diese Seite drucken

Balluff BCM R15E-00 DI00 S4 Serie Betriebsanleitung Seite 79

Condition monitoring sensor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
6
IO-Link interface (continued)
Index
Sub-
Access
index
VIBRATION VELOCITY RMS
0x2114
0x01
Read only
(8468)
(1)
0x02
Read only
(2)
0x03
Read only
(3)
0x04
Read only
(4)
VIBRATION VELOCITY PEAK TO PEAK
0x2115
0x01
Read only
(8469)
(1)
0x02
Read only
(2)
0x03
Read only
(3)
0x04
Read only
(4)
VIBRATION SEVERITY ZONE
0x2117
0x00
Read only
(8471)
(0)
VIBRATION VELOCITY STATISTICS X
0x2118
0x01
Read only
(8472)
(1)
0x02
Read only
(2)
0x03
Read only
(3)
0x04
Read only
(4)
0x05
Read only
(5)
www.balluff.com
Description
v-RMS X – Current RMS value of X-axis vibration
velocity in mm/s
v-RMS Y – Current RMS value of Y-axis vibration
velocity in mm/s
v-RMS Z – Current RMS value of Z-axis vibration
velocity in mm/s
v-RMS Magnitude – Current RMS value of vibration
velocity magnitude in mm/s
v-PEAK-TO-PEAK X – Current peak-to-peak value of
X-axis vibration velocity in mm/s
v-PEAK-TO-PEAK Y – Current peak-to-peak value of
Y-axis vibration velocity in mm/s
v-PEAK-TO-PEAK Z – Current peak-to-peak value of
Z-axis vibration velocity in mm/s
v-PEAK-TO-PEAK MAGNITUDE – Current peak-to-
peak value of vibration velocity magnitude in mm/s
SEVERITY ZONE – Current severity zone (see Severity
zone (SEVERITY ZONE) on page 37)
v-MEAN X – Mean of the vibration velocity value along
the X-axis over the selected time window. Value in
mm/s.
v-STANDARD DEVIATION X – Standard deviation of
the vibration velocity value along the X-axis over the
selected time window. Value in mm/s.
v-CREST FACTOR X – Crest factor of the vibration
velocity value along the X-axis over the selected time
window. Variable without units.
v-SKEWNESS X – Skewness of the vibration velocity
value along the X-axis over the selected time window.
Variable without units.
v-KURTOSIS X – Kurtosis of the vibration velocity value
along the X-axis over the selected time window.
Variable without units.
Data
Value
Default
type
range
value
float32
float32
float32
float32
float32
float32
float32
float32
uint2
float32
float32
float32
float32
float32
english
31