Condition monitoring sensor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
6
IO-Link interface (continued)
6.5
System commands
Different commands have been implemented in the BCM
which can be reached via the parameter SYSTEM
COMMAND on index 0x0002 (2), subindex 0x00 (0). If a
system command is transferred to the BCM, the command
triggers the desired action if permitted in the current
application state.
Command Name
0x80 (128)
DEVICE RESET
0x81 (129)
APPLICATION
RESET
0x82 (130)
RESTORE
FACTORY
SETTINGS
0xA5 (165)
MAINTENANCE
RESET
Tab. 6-22: System commands
www.balluff.com
Description
Performs a virtual restart
Restarts all modules,
OPERATION HOURS
SINCE STARTUP is set
to 0, BOOT CYCLE
COUNTER parameters
are not increased and
IO-Link communication
is maintained
Resets all configurations
to their factory settings
Resets the minimum
and maximum values of
all modules and
OPERATING HOURS
SINCE RESET and
BOOT CYCLE
COUNTER SINCE
RESET are set to 0
6.6
Device commands
Like system commands, the BCM also supports device
commands. These are transferred to parameter DEVICE
COMMAND on index 0x0064 (100) subindex 0x00 (0) and
are 32 bits long. The BCM supports the commands shown
in Tab. 6-23.
Command
Name
0x0000000B
RESET
(11)
DEVICE
1)
TEMPERA-
TURE
0x0000000C
RESET
(12)
CONTACT
TEMPERA-
TURE
0x0000000D
RESET
(13)
HUMIDITY
1)
0x0000000E
RESET
(14)
AMBIENT
1)
PRESSURE
0x00000020
START/STOP
(32)
PING
only for BCM R15E-002-DI00-_ _ , _-S4
1)
Tab. 6-23: Device commands
Description
Resets the minimum
and maximum values of
the device temperature
module
(index 0x0052 (82)
subindex 0x02 (2),
subindex 0x03 (3),
subindex 0x06 (6) and
subindex 0x07 (7))
Resets the minimum
and maximum values of
the contact temperature
module
(index 0x2031 (8241)
subindex 0x02 (2),
subindex 0x03 (3),
subindex 0x06 (6) and
subindex 0x07 (7))
Resets the minimum
and maximum values of
the relative humidity
module
(index 0x2041 (8257)
subindex 0x02 (2),
subindex 0x03 (3),
subindex 0x06 (6) and
subindex 0x07 (7))
Resets the minimum
and maximum values of
the ambient pressure
module
(index 0x2049 (8265)
subindex 0x02 (2),
subindex 0x03 (3),
subindex 0x06 (6) and
subindex 0x07 (7))
Activates or deactivates
the ping function
english
41