Balluff BCM R15E-00 DI00 S4 Serie Betriebsanleitung Seite 77

Condition monitoring sensor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BCM R15E-00 _ -DI00-_ _ , _-S4
Condition Monitoring Sensor
6
IO-Link interface (continued)
Index
Sub-
Access
index
VIBRATION VELOCITY ADVANCED ALARM CONFIGURATION
0x2107
0x01
Read/Write PRE-ALARM LEVEL v-RMS X – RMS value of the
(8455)
(1)
0x02
Read/Write MAIN-ALARM LEVEL v-RMS X – RMS value of the
(2)
0x03
Read/Write PRE-ALARM LEVEL v-RMS Y – RMS value of the
(3)
0x04
Read/Write MAIN-ALARM LEVEL v-RMS Y – RMS value of the
(4)
0x05
Read/Write PRE-ALARM LEVEL v-RMS Z – RMS value of the
(5)
0x06
Read/Write MAIN-ALARM LEVEL v-RMS Z – RMS value of the
(6)
0x07
Read/Write PRE-ALARM LEVEL v-RMS MAGNITUDE – RMS value
(7)
0x08
Read/Write MAIN-ALARM LEVEL v-RMS MAGNITUDE – RMS
(8)
0x09
Read/Write ENABLE ALARMS v-RMS X – Activates (True) or
(9)
0x0A
Read/Write ENABLE ALARMS v-RMS Y – Activates (True) or
(10)
0x0B
Read/Write ENABLE ALARMS v-RMS Z – Activates (True) or
(11)
0x0C
Read/Write ENABLE ALARMS v-RMS MAGNITUDE – Activates
(12)
www.balluff.com
Description
X-axis that must be exceeded in order to trigger
IO-Link event 0x8CF1 or set the corresponding status
bit. Value in mm/s.
X-axis that must be exceeded in order to trigger
IO-Link event 0x8CF2 or set the corresponding status
bit. Value in mm/s.
Y-axis that must be exceeded in order to trigger
IO-Link event 0x8CF1 or set the corresponding status
bit. Value in mm/s.
Y-axis that must be exceeded in order to trigger
IO-Link event 0x8CF2 or set the corresponding status
bit. Value in mm/s.
Z-axis that must be exceeded in order to trigger
IO-Link event 0x8CF1 or set the corresponding status
bit. Value in mm/s.
Z-axis that must be exceeded in order to trigger
IO-Link event 0x8CF2 or set the corresponding status
bit. Value in mm/s.
that the magnitude must exceed in order to trigger
IO-Link event 0x8CF1 or set the corresponding status
bit. Value in mm/s.
value that the magnitude must exceed in order to
trigger IO-Link event 0x8CF2 or set the corresponding
status bit. Value in mm/s.
deactivates (False) the sending of IO-Link events
(0x8CF1 and 0x8CF2) if the RMS value of the X-axis is
exceeded. The thresholds can be configured in
subindex 0x01 (1) and 0x02 (2).
deactivates (False) the sending of IO-Link events
(0x8CF1 and 0x8CF2) if the RMS value of the Y-axis is
exceeded. The thresholds can be configured in
subindex 0x03 (3) and 0x04 (4).
deactivates (False) the sending of IO-Link events
(0x8CF1 and 0x8CF2) if the RMS value of the Z-axis is
exceeded. The thresholds can be configured in
subindex 0x05 (5) and 0x06 (6).
(True) or deactivates (False) the sending of IO-Link
events (0x8CF1 and 0x8CF2) if the RMS value of the
magnitude is exceeded. The thresholds can be
configured in subindex 0x07 (7) and 0x08 (8).
Data
Value
Default
type
range
value
float32
0...12500
12500
[mm/s]
[mm/s]
float32
0...12500
12500
[mm/s]
[mm/s]
float32
0...12500
12500
[mm/s]
[mm/s]
float32
0...12500
12500
[mm/s]
[mm/s]
float32
0...12500
12500
[mm/s]
[mm/s]
float32
0...12500
12500
[mm/s]
[mm/s]
float32
0...12500
12500
[mm/s]
[mm/s]
float32
0...12500
12500
[mm/s]
[mm/s]
bool
True/False
True
bool
True/False
True
bool
True/False
True
bool
True/False
True
english
29