Note On Adding Refrigerant

CAUTION
・ Refrigerant charging must be performed after wiring, vacuuming, and the leak testing.
・ DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system.
Doing so can damage the unit or impact it's functioning.
・ Charging with unsuitable substances may cause explosions or accidents. Ensure that the
appropriate refrigerant is used.
Refrigerant containers must be opened slowly. Always use protective gear when charging the system.
・ DO NOT mix refrigerants types.
・ For the R290 or R32 refrigerant model, make sure the condtions within the area have been
made safe by control of flammable material when the refrigerant added into air conditioner.
・ The maximum refrigerant charge amount of R32 is 305 grams.
N=2(1 x 2 models), N=3(1 x 3 models), N=4(1 x 4 models), N=5(1 x 5 models). Depending on the
length of connective piping or the pressure of the evacuated system, you made need to add
refrigerant. Refer to table below for refrigerant amounts to be added:
Connective Pipe
Air Purging
Length(m)
Method
Pre-charge pipe length (ft/m)
Vacuum Pump
(Standard pipe length xN )
More than (Standard
Vacuum Pump
pipe lengthxN) ft/m
Note: The standard pipe length is 7.5m (24.6').
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Liquid Side: Ø 6.35 (Ø 1/4")
R32
(Total pipe length - standard pipe lengthxN) x12g/m
(Total pipe length - standard pipe lengthxN) x0.13oZ/ft
Additional Refrigerant(
R32:)
N/A
Liquid Side: Ø 9.52 (Ø 3/8")
R32
(Total pipe length - standard pipe lengthxN) x24g/m
(Total pipe length - standard pipe lengthxN) x0.26oZ/ft
Page 22