In this function transmitter output and
input readings are both scaled in
engineering units for quick
comparison. Transmitter may be a
linearized, non-linearized, 4-20 or
0-20 mA model for thermocouples
or RTD's.

Setting up a calibration

Setting up a calibration
Setting up a calibration
Setting up a calibration
Setting up a calibration
Leave the cursor on NONE in the
input menu and select the desired
output function.
Go through the menu and make the
selections as required. In the mode
screen, select CAL to calibrate a
transmitter. Proceed to select all
transmitter characteristics.
To check or calibrate
To check or calibrate
To check or calibrate
To check or calibrate
To check or calibrate
a transmitter
a transmitter
a transmitter
a transmitter
a transmitter
All normal keypad functions are
available to change the output. Use
the
key to change to fixed steps.
%
Use
and
keys to step through
#
$
0%, 25%, 50%, 75% and 100% of
the span as set-up. Press
return to the normal keypad functions.
An ideal transmitter will show
equal readings. The difference of
both readings is expressed in % of
the transmitter span or reading and
is shown in the upper window in
small size digits.
to
&