Faults, causes and remedies

Fault displays
Legend
Installation and operating instructions Wilo-Stratos GIGA, GIGA-D, GIGA B
Have faults remedied by qualified personnel only! Observe the
safety instructions in chapter 10 "Maintenance" on page 113.
• If the malfunction cannot be rectified, consult a specialist techni-
cian or the nearest customer service centre or representative
office.
For faults, causes and remedies, see the "Fault/warning message"
flow diagram in chapter 11.3 "Acknowledge fault" on page 122 and
the following tables. The first column of the table lists the code num-
bers displayed in the event of a fault.
NOTICE:
If the cause of the fault no longer exists, some faults resolve them-
selves automatically.
The following types of errors can occur with differing priorities
(1 = lowest priority; 6 = highest priority):
Error type Description
A
A fault exists; the pump stops immediately. The
fault must be acknowledged at the pump.
B
A fault exists; the pump stops immediately.
The counter is increased and a timer counts
down. After the 6th fault event, this becomes
a definite fault and has to be acknowledged at
the pump.
C
A fault exists; the pump stops immediately. If
the error exists for more than 5 min, the
counter is increased. After the 6th fault event,
this becomes a definite fault and has to be
acknowledged at the pump. Otherwise the
pump restarts automatically.
D
Like error type A, but error type A has a higher
priority than error type D.
E
Emergency operation: warning with
emergency operation speed and activated
SSM.
F
Warning – pump continues to turn.
(11-22kW)
English
Priority
6
5
4
3
2
1
119